FLAT PANEL/HEPA HIGH TEMPERATURE FILTER
- Description
Description
Features
Type | flat panel |
Frame | galvanized steel |
Filter media | glass fiber mat (white or yellow) |
Separators | continuous thermoplastic cord |
EN 779 Class | G4-F5 |
Average arrestance | 93%-96%(ASHRAE 52.1-1992) |
MERV | MERV 8-10(ASHRAE 52.2-1999) |
Protective Grids | galvanized steel or aluminium mesh |
UL 900 Standard | CLASS 2 |
Final pressure drop | (recommender) 200Pa -(maximum)250Pa |
Max. air flow rate | 125% of nominal air flow rate |
Max. operating temperature | 300℃ |
Max. relative humidity | 80% |
Applications | coarse particle filtration in ovens or high temperature air filtration |
Specification
Type | Class | Arrestance | Dimensions | Filtering surface (m2) | Rated air flow (m3/h) | Initial pressure drop (Pa) | ||
Length (mm) | Height (mm) | Depth (mm) | ||||||
HTB-90 | G4 | 94% | 480 | 480 | 15 | 0.22 | 1000 | 70 |
HTB-90 | G4 | 94% | 500 | 500 | 15 | 0.24 | 1000 | 70 |
HTB-90 | G4 | 93% | 500 | 500 | 25 | 0.24 | 2000 | 100 |
HTB-90 | G4 | 93% | 500 | 500 | 50 | 0.24 | 2000 | 90 |
HTB-55 | F5 | 96% | 480 | 480 | 10 | 0.22 | 1000 | 60 |
HTB-55 | F5 | 96% | 500 | 500 | 10 | 0.24 | 1000 | 60 |
HTB-55 | F5 | 95% | 500 | 500 | 25 | 0.24 | 2000 | 140 |
HTB-55 | F5 | 95% | 500 | 500 | 50 | 0.24 | 2000 | 120 |